# C&S WHOLESALE GROCERS - ABERDEEN
> **Administrative - Formal** · FY2008 · — · Final Order With Penalty
## Case
- **Activity ID:** `1000005985`
- **Case Number:** 03-2008-0159
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- C&S WHOLESALE GROCERS (complaint) (settlement)
## Summary

THE FACILITY WAS CHOSEN FOR INSPECTION DUE TO A RELEASE OF AMMONIA ON JULY 5, 2006.  THERE A 2 SENSORS IN THE COMPRESSOR ROOM THAT ARE SET AT 50 PPM (WARNING) AND 150 PPM (ALARM).  SENSORS ARE INTERLOCKED WITH FANS AND THE KING VALVE SOLENOID; LIGHTS ARE ACTIVATED AND CALL DOWN SEQUENCE ACTIVATED.  FACILITY PERSONNEL STATED THAT SENSORS WERE TESTED AND CALIBRATED ANNUALLY.  THE SENSORS WERE TESTED BY FACILITY AND EPA PERSONNEL; BOTH MANNING SENORS DID NOT WORK.

---