# BIBB COUNTY (GA) LAW ENFORCEMENT CENTER
> **Administrative - Formal** · FY2003 · — · Final Order With Penalty
## Case
- **Activity ID:** `105005`
- **Case Number:** 04-2003-0005
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- BIBB COUNTY BOARD OF COMMISSIONERS (complaint) (settlement)
## Summary

9/30/03 - COMPLAINT FILED, PROPOSING A PENALTY OF $71,740.   COMPLAINT ALLEGES:

RESPONDENT FAILED TO ENSURE THAT ITS UST WAS STRUCTURALLY SOUND BEFORE INSTALLING A CATHODIC PROTECTION SYSTEM, IN VIOLATION OF RCRA 9006;

RESPONDENT FAILED TO HAVE ITS CATHODIC PROTECTION SYSTEM TESTED BY A QUALIFIED CATHODIC PROTECTION TESTER WITHIN 6 MONTHS OF INSTALLATION AND EVERY 3 YEARS THEREAFTER, IN VIOLATION OF RCRA 9003;

RESPONDENT FAILED TO INSPECT ITS IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM TO ENSURE PROPER OPERATION AT LEAST EVERY 60 DAYS, IN VIOLATION OF RCRA 9003;

RESPONDENT FAILED TO OPERATE ITS IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUOUSLY FOR CORROSION PROTECTION, IN VIOLATION OF RCRA 9003;

RESPONDENT FAILED TO MAINTAIN RECORDS OF OPERATION OF THE CATHODIC PROTECTION SYSTEM, IN VIOLATION OF RCRA 9003;

RESPONDENT FAILED TO PROVIDE ADEQUATE RELEASE DETECTION FOR ITS UST SYSTEM, IN VIOLATION OF RCRA 9003;

RESPONDENT FAILED TO MONITOR ITS USTs FOR RELEASES EVERY 30 DAYS, IN VIOLATION OF RCRA 9003;

RESPNDENT FAILED TO PROVIDE AN ADEQUATE AUTOMATIC LEAK DETECTION SYSTEM FOR ITS PRESSURIZED PIPING, IN VIOLATION OF RCRA 9003;

RESPONDENT FAILED TO MAINTAIN ANY RECORDS OF RELEASE DETECTION FOR ITS USTs AND ASSOCIATED PIPING, IN VIOLATION OF RCRA 9

---