MUNICIPALLY OPERATED INTERNATIONAL AIRPORT W/STORAGE SITE FOR PCB TRANSFORMERS OPERATED BY CITY DEPARTMENT OF PUBLIC WORKS. A NOVEMBER 18, 1993 INSPECTION FOUND PCB TRANSFORMERS BEING STORED IN AN AREA WITHOUT ADEQUATE CONTAINMENT; ACCESS TO AREA NOT MARKED WITH PCB LABEL; NOT DATED WHEN PLACED IN STORAGE FOR DISPOSAL; CITY DID NOT APPLY FOR AND RECEIVE EPA ID #. TOTAL PENALTY IS $49,000 FOR VIOLATIONS OF: 40 CFR SECTIONS 761.40(A)(10), 761.65(B)(1), 761.65(C)(8). THE MULTI-MEDIA SCREENING REVEALED NO OTHER ACTIVITY AND NO TRI RELEASES.