# WILDWOOD GOLF COURSE
> **Administrative - Formal** · FY2001 · — · Final Order With Penalty
## Case
- **Activity ID:** `32851`
- **Case Number:** 05-2001-0188
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** $650
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** N
## Defendants
- WILDWOOD GOLF COURSE (settlement)
## Summary

THE WILDWOOD GOLF COURSE HAS A MAINTENANCE GARAGE FOR THE    EQUIPMENT IT USES TO MAINTAIN THE GOLF COURSE.  THE FACILITY HAS A NINE-YEAR OLD 550-GAL STI-P3 GASOLINE UST.  THE FACILI TY IS LOCATED IN A POPULAR SUBURBAN AREA.  SENSITIVE ECO-    SYSTEM NEARBY IS UNKNOWN.  THE FACILITY FAILED TO CONDUCT CP TESTING AND LEAK DETECTION MONITORING SINCE INSTALLATION.    THE INSPECTORS CONDUCTED CP TEST WHICH INDICATED THAT THE    TANK WAS MADE OF STEEL.  ALTHOUGH THE INSPECTORS' TEST       RESULTS CONFIRMED THAT THE TANK WAS STILL CATHODICALLY PRO-  TECTED, THE FACILITY IS REQUIRED TO CONDUCT A CP TEST EVERY  THREE YEARS PER THE REGULATIONS.  BASED ON THE VIOLATIONS    FOUND, THE WILDWOOD GOLF COURSE WAS ISSUED A FIELD CITATION  FOR THE AMOUNT OF $650.00 FOR THE FOLLOWING VIOLATIONS.      1. 40CFR 280.45 - FAILURE TO MAINTAIN RECORD OF RELEASE      DETECTION MONITORING - $150.00                               2. 40 CFR 280.40(A) - FAILURE TO PROVIDE ADEQUATE RELEASE    DETECTION METHOD - $300.00                                   3.  40 CFR 280.31(B) - FAILURE TO ENSURE PROPER OPERATION OF CATHODIC PROTECTION SYSTEM - %150.00                         4. 40 CFR 280.31(D) - FAILURE TO MAINTAIN RECORDS OF CATHO-  DIC PROTECTION INSPECTIONS - $50.00                          THE FACILITY TOOK THE NECESSARY MEASURES TO RETURN TO COM-   PLIANCE.  CP TEST WAS CONDUCTED AND AN ATG SYSTEM WAS        INSTALLED FOR LD.

---
*Source: [EPA ECHO](https://echo.epa.gov/) · AI Analytics · CC0 1.0*