ERGON REFINING, INC.

Administrative - Formal · FY2013 · — · Final Order With Penalty · 3400054907

Penalty
Cost recovery
Compliance action

Case

Case Number
04-2013-7002
Type
Administrative - Formal
Lead
EPA
Outcome
Final Order With Penalty
Multimedia
Self-disclosure
N

Defendants (1)

Summary

2/12/13 - CONSENT AGMT AND FINAL ORDER ISSUED, ASSESSING PENALTY OF $8,600, DUE W/IN 30 DAYS. ALLEGATIONS: ON JAN 13, 2010, AN INSPECTION WAS CONDUCTED BY EPA AT RESPONDENT'S FACILITY TO DETERMINE COMPLIANCE WITH SPCC REGS. EPA ALLEGES: A. 40 CFR 112.7: THIS REG REQUIRES THAT AN SPCC PLAN FOLLOW THE SEQUENCE OF THE RULE OR INCLUDE A DETAILED CROSS-REFERENCE OF REQUIREMENTS IN THE SPCC PLAN WITH THE SPCC RULES. HOWEVER, RESPONDENT'S SPCC PLAN DID NOT FOLLOW THE SEQUENCE OF THE RULE OR INCLUDE A DETAILED CROSS-REFERENCE OF THE REQUIREMENTS IN THE PLAN AS REQUIRED BY 40 CR 112.7. B. 40 CFR 112.7(b): THIS REG REQUIRES THAT, WHERE EXPERIENCE INDICATES A REASONABLE POTENTIAL FOR EQUIPMENT FAILURE, AN SPECC PLAN MUST PREDICT THE DIRECTION, RATE OF FLOW, AND TOTAL QUANTITY OF OIL WHICH COULD BE DISCHARGED FROM THE FACILITY AS A RESULT OF EACH TYPE OF MAJOR EQUIPMENT FAILURE. HOWEVER, RESPONDENT'S SPCC PLAN DID NOT INLCUDE A PREDITION OF THE RATE OF FLOW FOR THE TOTAL QUANTITY OF OIL THAT COULD BE DISCHARGED FROM EACH TYPE OF MAJOR EQUPMENT FAILURE. C. 40 CFR 112.7(c): THIS REG, AND 40 CFR 112.7(a)(1), REQUIRES AN SPCC PLAN TO DISCUSS CONTAINMENT METHODS FOR OIL FILLED OPERATIONAL EQUIPMENT AT A FACILITY. HOWEVER, RESPONDENT'S SPCC PLAN DID NOT DISCUSS CONTAINMENT METHODS FOR OIL FILLED PIPING AT ITS FACILITY. D. 40 CFR 112.7(g): THIS REG REQUIRES AN SPCC PLAN TO DISCUSS SECURITY MECHANISMS FOR ITS FACILITY. SPECIFICALLY, AN SPCC PLAN MUST DESCRIBE HOW A FACILITY SECUR

Source

Authoritative
EPA ECHO
Machine
JSON-LD · Markdown