4/14/2015 - EXPEDITED SETTLEMENT AGREEMENT ISSUED, ASSESSING A PENALTY OF $8,940.
AGREEMENT ALLEGES:
CORNER PANTRY115
RELEASE DETECTION (TANKS)
RESPONDENT FAILED TO MONITOR TANK #5 AT CORNER PANTRY 115 AT LEAST ONCE EVERY 30 DAYS. IN VIOLATION OF S.C. CODE ANN. REGS. 61-92.280.41(a)] [40 CFR SECTION 280.41(a)].
RELEASE DETECTION (PIPING - ANNUAL LINE TIGHTNESS TEST)
RESPONDENT FAILED TO CONDUCT TO AN ANNUAL LINE TIGHTNESS TEST OR PERFORM MONTHLY MONITORING ON PRESSURIZED PIPING FOR TANK #5. IN VIOLATION OF S.C. CODE ANN. REGS. 61-92.280.41(b)(1) [40 CFR SECTION 280.41(b)(1)].
RELEASE DETECTION (PIPING - ANNUAL LINE LEAK DETECTOR TEST)
RESPONDENT IS IN VIOLATION OF S.C. CODE ANN. REGS. 61-92.280.44(a) [40 CFR SECTION 280.44(a)RESPONDENT FAILED TO CONDUCT AN ANNUAL TEST OF THE OPERATION OF THE LINE LEAK DETECTOR IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENT, FOR TANK #5 AT CORNER PANTRY 115.
CORNER PANTRY 116
RELEASE DETECTION (TANKS)
RESPONDENT FAILED TO MONITOR TANK #4 AT CORNER PANTRY #4 AT CORNER PANTRY 116 AT LEAST ONCE EVERY 30 DAYS. IN VIOLATION S.C. ANN. REGS. 61-92.280.41(a) [40 CFR SECTION 280.41(a)].
SPILL PREVENTION (SPILL BUCKET)
RESPONDENT FAILED TO PROVIDE AN ADEQUATE METHOD OF SPILL PREVENTION FOR TANK #1 AT CORNER PANTRY 116. IN VIOLATION OF S.C. CODE ANN. REGS 61-92.280.21(d) [40 CFR SECTION 280.21(d)].
OVERFILLE PREVENTION (FLAPPER VALVE)
RESPONDENT FAILED TO PROVIDE AN ADEQUATE METHOD OF OVERFILL PREVENTION FOR TANK 4 AT C