# HIGH LINER FOODS USA, INC.
> **Administrative - Formal** · FY2016 · — · Final Order With Penalty
## Case
- **Activity ID:** `3600776623`
- **Case Number:** 03-2016-0162
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- HIGH LINER FOODS USA, INC. (complaint) (settlement)
## Summary

on April 21, 2016, an authorized representative of the EPA conducted an inspection of the High Liner Foods USA. Inc. facility located at 190 Enterprise Drive In Newport News. VA. to determine compliance with the Risk Management Plan (RMP) regulations promulgated at 40 C.F.R. Part 68 under Section 112(r) of the Clean Air Act (the Act or CAA). EPA found that the Respondent had violated regulations implementing Section 112(r) of the Act specifically: The owner or operator has not documented that equipment complies with recognized and generally accepted good engineering practices in accordance with 40 CFR 68.65(d)(2). Relief venting was Installed adjacent to a condenser platform less than 7.25' above the platform level required by industry standard IIAR 2 (2014).

---