# DIMOND CENTER (COE)
> **Administrative - Formal** · FY2016 · — · —
## Case
- **Activity ID:** `3600785084`
- **Case Number:** 10-2016-9001
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** —
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- DIMOND CENTER (complaint) (settlement)
## Summary

Dimond violated 40 C.F.R. 82.15(b)(1) when it imported approximately 2,267 kilograms of HCFC-22 for which it had not been apportioned any baseline consumption allowance under 40 C.F.R. 82.19.  Further, Dimond failed:  1, to repair the industrial process refrigeration appliance such that the annual leak rate was reduced below 35 percent; 2, to repair leaks within 30 days after discovery; 3, to perform initial verification tests and follow-up verification tests; 4, to develop retrofit or retirement plans; 5, to retrofit or retire the industrial process refrigeration appliance; 6, to notify EPA after repairs on the industrial process refrigeration appliance failed to bring the leak rates below 35 percent; and 7, to maintain records of the dates, types, and results of all initial and follow-up verification tests performed.

---