← EPA enforcement cases

HERSHEY CREAMERY COMPANY (HERSHEY CREAMERY COMPANY-MIDDLETOWN)

Administrative - Formal · FY2017 · — · Final Order With Penalty · 3601007243

Penalty
Cost recovery
Compliance action

Case

Case Number
03-2017-0098
Type
Administrative - Formal
Lead
EPA
Outcome
Final Order With Penalty
Multimedia
Self-disclosure
N

Defendants (1)

Summary

On December 7, 2016 an authorized representative of the EPA conducted an inspection of the Hershey Creamery Co. Middletown facility located at 1200 AIP Drive in Middletown. PA, to determine compliance with the Risk Management Plan (RMP) regulations promulgated at 40 C.F .R. Part 68 under Section 112(r) of the Clean Air Act (the Act or CAA). EPA found that the Respondent had violated regulations implementing Section 112(r) of the Act, specifically: (1) Failure of the Owner/Operator to document that their equipment complies with generally accepted good engineering practices namely that their ammonia machinery room has visual and audible alarm annunciation outside each entrance to their refrigeration machinery room in accordance with 68.65(d)(2) and ANSI/ASHRAE Standard 15 Safety Standard for Ammonia Refrigeration Systems.

Source

Authoritative
EPA ECHO
Machine
JSON-LD · Markdown