ON DECEMBER 13, 2016, EPA INSPECTORS CONDUCTED AN INSPECTION OF THE TUSCAN / LEHIGH DAIRIES, INC.FACILITY LOCATED AT 880 ALLENTOWN ROAD, LANSDALE, PA TO DETERMINE COMPLIANCE WITH THE RISK MANAGEMENT PLAN (RMP) REGULATIONS PROMULGATED AT 40 C.F.R. PART 68 UNDER SECTION 112(r) OF THE CLEAN AIR ACT (THE ACT, CAA). EPA FOUND THAT THE RESPONDENT HAD VIOLATED REGULATION IMPLENTING SECTION 112(r() OF THE ACT, SPECIFICALLY, THE FACILITY FAILED TO DOCUMENT THE EQUIPMENT COMPLIED WITH RECOGNIZING AND GENERALLY ACCEPTING GOOD ENGINEERING PRACTICES IN ACCORDANCE WITH 40 C.F.R. SECTION 68.65(d)(2). IT WAS FOUND THAT 1) AUDIBLE AND VISUAL ALARMS WERE NOT PRESENT OUTSIDE ENTRANCES TO THE REFRIGERATED MACHINERY ROOM AND 2) REFRIGERATED MACHINERY ROOM DID NOT OPEN OUTWARD AND WERE NOT TIGHT-FITTING.