# RM COMMERCIAL
> **Administrative - Formal** · FY2020 · — · Final Order With Penalty
## Case
- **Activity ID:** `3602216203`
- **Case Number:** 04-2020-3201
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- RM COMMERCIAL (complaint) (settlement)
## Summary

6/3/2020 - CONSENT AGREEMENT AND FINAL ORDER ISSUED, ASSESSING A PENALTY OF $41,300 DUE WITHIN 30 DAYS. 

ALLEGATIONS:  RESPONDENT WAS STORING THE FOLLOWING PCB ITEMS FOR DISPOSAL: PCB Items in storage are required to be checked for leaks at least once every 30 days. Records of those inspections are required to be maintained. During the November 19, 2019 inspection, the EPA inspector determined that the Respondent had not conducted or documented any inspections of the PCB Items listed. 

A written annual document log and annual records are required for anyone that uses or stores at least 45 kilograms of PCBs contained in  PCB  Container(s), or one or more PCB Transformers or 50 or more PCB Large High or Low Voltage Capacitors. The log must be prepared by July 1 for the previous calendar year and maintained for three years after PCBs are ceased being used or stored.  At the time of the November 19, 2019 inspection, Respondent did not have any written annual document  logs and/or  annual  records. 

PCB Items designated for disposal must be stored in an area with an adequate root, walls, and non-porous near with curbing. At the time of the November 19, 2019 inspection, Respondent was storing the PCB items for disposal in areas that did not meet the requirements. 

PCB Transformers at the time of manufacture, at the time of distribution in commerce if not already marked and at the time or removal from use if not already marked, shall be marked with an M marking. At the t

---