On June 13, 2019, a representative of EPA conducted an inspection of the Respondent facility. Respondent failed to compile complete information regarding safety systems for the wastewater chlorination process, a violation of 40 CFR 68.65(a) and (d). A copy of the Water Chlorination Process PHA submitted to EPA failed to address stationary source siting, a violation of 68.67(c). Respondent violated 40 CFR 68.69(a) by not developing written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information. The Respondent failed to certify the operating procedures for 2017, 2018, and 2019, a violation of 68.69(c). Respondent violated 40 CFR 68.71 by failing to train certain employees, and/or failed to provide training documentation for certain employees involved in the operation of the wastewater chlorination process.