# Valero Meraux-RMP GDC Incident CAFO-FY2021
> **Administrative - Formal** · FY2021 · — · Final Order With Penalty
## Case
- **Activity ID:** `3602475043`
- **Case Number:** 06-2021-3311
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- Valero Refining-Meraux, LLC (complaint) (settlement)
## Summary

The facility had a release incident on 04/10/2020, when an operator did not properly implement the site's Safety System Bypass Procedure.  When attempting to reseat a pressure safety valve (PSV). Instead of closing the upstream high-pressure valve to relieve pressure on the PSV, the downstream low-pressure valve was closed, resulting in an overpressure and subsequent release of high-pressure hydrocarbon from the
downstream valve bonnet. Failure to follow the Safety System Bypass Procedure is a violation of 40 CFR 68.69(a), Operating Procedures.

---