# ERNIE'S FUEL STOPS
> **Administrative - Formal** · FY2023 · — · Final Order With Penalty
## Case
- **Activity ID:** `3603698097`
- **Case Number:** 10-2023-0163
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- ERNIE'S FUEL STOPS (complaint) (settlement)
## Summary

Automatic line leak detectors were not tested for 2 years, the overfill prevention device had not been inspected at least once every 3 years, and the tightness test of the spill buckets had not been done within the last 3 years. During testing of the diesel line, the valve cracked while trying to get the valve free. The diesel product lines were manifolded. A new company took over operations of the facility and installed new product lines, submersible turbine pumps, under dispenser containment, spill buckets and overfill devices.

---