# U.S. Army; Fort Bragg Military Installation (UST)
> **Administrative - Formal** · FY2002 · — · Final Order With Penalty
## Case
- **Activity ID:** `88235`
- **Case Number:** 04-2002-0002
- **Type:** Administrative - Formal
- **Lead:** EPA
- **Outcome:** Final Order With Penalty
- **Penalty assessed:** —
- **Cost recovery:** —
- **Compliance action $:** —
- **Multimedia (multi-env):** —
## Defendants
- Fort Bragg Military Installation (complaint) (settlement)
- U.S. Army (complaint) (settlement)
## Summary

'9/30/02 - Complaint filed, proposing a penalty of $33,673.  Complaint alleges that Respondent failed to provide release detection capable of detecting a release from an UST and associated piping that routinely carries regulated substances UST systems; respondent failed to provide overfill prevention equipment capable of preventing overfilings associated with product transfer to the UST system; Respondent failed to provide spill protection capable of containing spills associated with product transfer for UST systems; respondent failed to operate and maintain cathodic protection systems to protect UST system; respondent failed to inspect the impressed current corrosion protection system every 60 days for UST systems; respondent failed to test the cathodic protection systems 6 months after installation and every three years thereafter for UST systems

---