FACILITY WAS ISSUED AN UST FIELD CITATION FOR FAILURE TO COMPLY W/ THE FOLLOWING REQUIREMENTS: 40 CFR 280.41(A): FAILURE TO MONITOR TANKS FOR RELEASES AT LEAST EVERY 30DAYS; 280.41(B)(1)(II): FAILURE TO HAVE ANNUAL LINE TIGHTNESS TEST OR PERFORM MONTHLY MONITORING ON PRESSURIZED PIPING; 280.44(A): FAILURE TO CONDUCT ANNUAL TEST OF LINE LEAK DE- TECTOR SYSTEM FOR UNDERGROUND PIPING; 280.31(B): FAILURE TO ENSURE PROPER OPERATION OF CATHODIC PROTECTION SYSTEM; 280.31(C): FAILURE TO INSPECT IMPRESSED CURRENT SYSTEM EVERY 60 DAYS; 280.34(B)(2): FAILURE TO MAINTAIN CORROSION PRO- TECTION EQUIPMENT OPERATION DOCUMENTATION; 280.34(C)(1): FAILURE TO MAINTAIN RECORDS AT UST SITE AND IMMEDIATELY AVAILABLE FOR INSPECTION. WHILE THE FACILITY OWNER PROVIDED WITH THE SIGNED FC AND FC PAYMENT, HE DID NOT PROVIDE ANY COMPLIANCE DOCUMENTS. PROOF OF COMPLIANCE RESTS WITH HIS SIGNED FC. *