# ELECTRICAL
> MSHA accident `220030590028` · 02/17/2003 · Rinker Materials Of Florida, Inc
## Details
- **Degree of injury:** DAYS RESTRICTED ACTIVITY ONLY
- **Classification:** ELECTRICAL
- **Accident type:** Contact with electrical current
- **Occupation:** Electrician, Lineman
- **Activity:** Electrical maintenance
- **Injury source:** CONDCTR,ELCT,CBL,TROL POL
- **Nature of injury:** ELECTRIC BURN-CNTACT BURN
- **Body part:** UPPER EXTREMITIES, MULTIPLE
- **Days lost:** —
- **Mine experience:** 0.23 years
## Operator
- **Controller:** CSR Ltd
- **Operator:** Rinker Materials Of Florida, Inc
- **Mine:** [0800024](https://api.ai-analytics.org/mine/0800024)
## Narrative

WHILE TROUBLE SHOOTING A 4150 MAIN BREAKER PANEL, EE MAD CONTACT WITH 4160 VOLTS IN THE BUS BAR PANEL NEXT TO THE MAIN BREAKER. EE FAILED TO FOLLOW POSTED PROCEDURES BY VISUAL CONFIRMATION THA T THE KNIFE SWITCHES FOR THE BREAKER WERE DISENGAGED EVEN THOUGH THE MAIN BREAKERE SWITCH WAS IN THE OFF POSITION. THE BREAKER SWITCH SHAFT WAS BROKEN.

---
*Source: [MSHA Open Government Data](https://arlweb.msha.gov/OpenGovernmentData/) · AI Analytics · CC0 1.0*