# ELECTRICAL
> MSHA accident `220052690048` · 09/15/2005 · Mosaic Fertilizer, LLC
## Details
- **Degree of injury:** DYS AWY FRM WRK & RESTRCTD ACT
- **Classification:** ELECTRICAL
- **Accident type:** Contact with electrical current
- **Occupation:** Electrician, Lineman
- **Activity:** Electrical maintenance
- **Injury source:** ELECTRICAL APPARATUS,NEC
- **Nature of injury:** ELECTRIC BURN-CNTACT BURN
- **Body part:** MULTIPLE PARTS (MORE THAN ONE MAJOR)
- **Days lost:** 43
- **Mine experience:** 8.19 years
## Operator
- **Controller:** Mosaic Company
- **Operator:** Mosaic Fertilizer, LLC
- **Mine:** [0801117](https://api.ai-analytics.org/mine/0801117)
## Narrative

Electrician was reversing motor for mechanic to remove impeller. Impeller was removed & electrician went back to reverse motor leads when his left arm came in contact with line side 4160V contactor. (Knife blades) Three phases on disconnect were still in closed position.

---
*Source: [MSHA Open Government Data](https://arlweb.msha.gov/OpenGovernmentData/) · AI Analytics · CC0 1.0*