# ELECTRICAL
> MSHA accident `220052930009` · 10/10/2005 · Rogers Group Inc
## Details
- **Degree of injury:** DAYS AWAY FROM WORK ONLY
- **Classification:** ELECTRICAL
- **Accident type:** Flash burns (electric)
- **Occupation:** Electrician, Lineman
- **Activity:** Electrical maintenance
- **Injury source:** ELECTRICAL APPARATUS,NEC
- **Nature of injury:** ELECT.ARC BURN-NOT CONTAC
- **Body part:** MULTIPLE PARTS (MORE THAN ONE MAJOR)
- **Days lost:** 35
- **Mine experience:** 3 years
## Operator
- **Controller:** Rogers Group Inc
- **Operator:** Rogers Group Inc
- **Mine:** [1200721](https://api.ai-analytics.org/mine/1200721)
## Narrative

Working on disconnect knives of a motor starter bucket in a motor control center. Power was on. Employee inadvertently placed screwdriver on energized knife and door saftey catch of motor control bucket. Injury was arc flash burn to right and left hand and face. The said bucket was on the bottom and employee was laying on left side during the repair.

---