← MSHA accidents

ELECTRICAL

220053430060 · 12/06/2005 · —

Details

Degree of injury
DAYS AWAY FROM WORK ONLY
Classification
ELECTRICAL
Accident type
Flash burns (electric)
Occupation
Maintenance man, Mechanic, Repair/Serviceman, Boilermaker, Fueler, Tire tech, Field service tech
Activity
Electrical maintenance
Injury source
ELECTRICAL APPARATUS,NEC
Nature of injury
ELECT.ARC BURN-NOT CONTAC
Body part
MULTIPLE PARTS (MORE THAN ONE MAJOR)
Days lost
135
Mine experience
25.69 years

Operator

Controller (parent)
Operator
Mine
4103659

Narrative

2 EMPLOYEES RECEIVED BURN INJURIES TO THEIR PERSONS WHEN A SUBSTATION EXPLODED. THE CONTRIBUTING FACTORS WERE THE ELECTRICIAN FORGOT TO REMOVE THE GROUND STRAPS FROM AN AIR SWITCH & A PHASE CONDITION OCCURRED WHEN THE OIL CIRCUIT BREAKER WAS CLOSED. THE OCB OPENED BUT FAILED TO EXTINGUSH THE ARC ON TWO PHASES WHICH CAUSED AN EXPLOSION.