# ELECTRICAL
> MSHA accident `220062500036` · 07/31/2006 · Climax Molybdenum Company
## Details
- **Degree of injury:** DAYS AWAY FROM WORK ONLY
- **Classification:** ELECTRICAL
- **Accident type:** Contact with electrical current
- **Occupation:** Maintenance man, Mechanic,  Repair/Serviceman, Boilermaker, Fueler, Tire tech, Field service tech
- **Activity:** Electrical maintenance
- **Injury source:** CONDCTR,ELCT,CBL,TROL POL
- **Nature of injury:** ELECT SHOCK,ELECTROCUTION
- **Body part:** BODY SYSTEMS
- **Days lost:** 29
- **Mine experience:** 0.58 years
## Operator
- **Controller:** Phelps Dodge Corp
- **Operator:** Climax Molybdenum Company
- **Mine:** [0500790](https://api.ai-analytics.org/mine/0500790)
## Narrative

Employee was changing out a feed cable on the boom of a Tamrock bolter. The bolter was plugged into a power source. The trailing cable was energized from a distance by an electrician who could not see the bolter. The plug from the disconnect had one phase to ground. When the feed cable was energized, the mechanic was in connect with the bolter and recieved a shock.

---
*Source: [MSHA Open Government Data](https://arlweb.msha.gov/OpenGovernmentData/) · AI Analytics · CC0 1.0*