# ELECTRICAL
> MSHA accident `220072260041` · 08/12/2007 · BHP Copper Inc
## Details
- **Degree of injury:** DAYS RESTRICTED ACTIVITY ONLY
- **Classification:** ELECTRICAL
- **Accident type:** Contact with electrical current
- **Occupation:** Wireman, Communications man
- **Activity:** Electrical maintenance
- **Injury source:** ELECTRICAL APPARATUS,NEC
- **Nature of injury:** ELECTRIC BURN-CNTACT BURN
- **Body part:** UPPER EXTREMITIES, MULTIPLE
- **Days lost:** 0
- **Mine experience:** 0.08 years
## Operator
- **Controller:** Broken Hill Proprietary Company Ltd
- **Operator:** BHP Copper Inc
- **Mine:** [0201049](https://api.ai-analytics.org/mine/0201049)
## Narrative

Terminating cable in cubicle after locking out and removing starter from cubicle. Cable was being routed into position when right index finger contacted energized P.T., exiting right forearm 4"" below elbow. P.T.'s connected to starter via stab-in fingers on breaker. Load side of cubicle was checked for voltage and found de-energized. P.T.'s assumed de-energized.

---