← MSHA accidents

ELECTRICAL

220073200023 · 11/15/2007 · National Cement Company Of California Inc

Details

Degree of injury
ACCIDENT ONLY
Classification
ELECTRICAL
Accident type
Accident type, without injuries
Occupation
—
Activity
—
Injury source
—
Nature of injury
—
Body part
—
Days lost
0
Mine experience
— years

Operator

Controller (parent)
Vicat S A
Operator
National Cement Company Of California Inc
Mine
0400213

Narrative

Employee was racking out motor switch gear for fan # 71FA07 at MCC J. He checked with the control room and asked if it was okay to lock it out, but failed to check the guages to verify the switch gear was not under power. The employee disengaged a 4160 volt switch under load causing an arc flash and destroying the breaker. The employee was not injured.

Source

Authoritative
MSHA Open Government Data
Machine