← MSHA accidents
ELECTRICAL
220200520015 · 02/11/2020 · Lehigh Southwest Cement Co.
Details
Degree of injury NO DYS AWY FRM WRK,NO RSTR ACT
Classification ELECTRICAL
Accident type Flash burns (electric)
Occupation Electrician, Lineman
Activity Hand tools (powered)
Injury source ELECTRICAL APPARATUS,NEC
Nature of injury ELECT.ARC BURN-NOT CONTAC
Body part MULTIPLE PARTS (MORE THAN ONE MAJOR)
Days lost 0
Mine experience 2.71 years
Operator
Controller (parent) Heidelberg Materials AG
Operator Lehigh Southwest Cement Co.
Mine 0404075
Narrative Electrician opened an electrical panel which contained a 4160v line. The employee tested the line with an instrument rated for 1000v. The employee received first degree burns to arms and face.