# FIRE
> MSHA accident `220213000004` · 10/23/2021 · U.S. Silver-Idaho, Inc.
## Details
- **Degree of injury:** ACCIDENT ONLY
- **Classification:** FIRE
- **Accident type:** Accident type, without injuries
- **Occupation:** —
- **Activity:** —
- **Injury source:** —
- **Nature of injury:** —
- **Body part:** —
- **Days lost:** —
- **Mine experience:** — years
## Operator
- **Controller:** Americas Gold and Silver Corporation
- **Operator:** U.S. Silver-Idaho, Inc.
- **Mine:** [1000082](https://api.ai-analytics.org/mine/1000082)
## Narrative

The pump failed causing one of the fuses to blow in the pump starter, and because the starter did not trip it caused the motor to single-phase which caused the #3 Station Sub 600 amp disconnect to blow a fuse. The 600 amp disconnect in the Sub on the #3 station is burned up and needs to be replaced and 700HP pump burned up where fire started.  

---
*Source: [MSHA Open Government Data](https://arlweb.msha.gov/OpenGovernmentData/) · AI Analytics · CC0 1.0*