# ELECTRICAL
> MSHA accident `220221870010` · 06/26/2022 · Imerys Filtration Minerals, Inc.
## Details
- **Degree of injury:** DAYS AWAY FROM WORK ONLY
- **Classification:** ELECTRICAL
- **Accident type:** Flash burns (electric)
- **Occupation:** Electrician, Lineman
- **Activity:** Electrical maintenance
- **Injury source:** ELECTRICAL APPARATUS,NEC
- **Nature of injury:** ELECT.ARC BURN-NOT CONTAC
- **Body part:** MULTIPLE PARTS (MORE THAN ONE MAJOR)
- **Days lost:** 7
- **Mine experience:** 4.1 years
## Operator
- **Controller:** Imerys S A
- **Operator:** Imerys Filtration Minerals, Inc.
- **Mine:** [0402848](https://api.ai-analytics.org/mine/0402848)
## Narrative

Worker was turning on a VFD. When the electrician engaged the switch EE saw a flash and heard a loud bang. The breaker worked and arc was inside cabinet. Previously during a maintenance work a panel was installed with a self taping screw that punctured a cord. When the system was energized it went to ground and caused and arc inside the cabinet.  

---