# NRC CAL – NOV (White / SLIII)
> **EA-10-205** · CAL · Severity SLIII · Issued 2010-12-07 · Reactor Licensees
## Action
- **EA Number:** EA-10-205
- **Licensee:** NOV (White / SLIII)
- **Category:** Reactor Licensees
- **Action type:** CAL
- **Severity level:** SLIII
- **Date issued:** 2010-12-07
## Description

On December 7, 2010, the NRC issued a White finding with associated violation and Notice of Violation (NOV) for a Severity Level III violation to Carolina Power and Light Company (doing business as Progress Energy Carolinas Inc (PEC)) as a result of inspections at the H.B. Robinson Steam Electric Plant Unit 2. The White finding involved the failure to identify and correct a problem associated with the "B" Emergency Diesel Generator (EDG) output breaker in 2008. Again in 2009, a similar malfunction caused the EDG to be declared inoperable for a period greater than Technical Specifications. A 10 CFR 50.9, "Completeness and Accuracy of Information," NOV for a Severity Level III violation was also assessed for submitting materially inaccurate information. PEC provided information which stated that the breaker was tested in accordance with a maintenance procedure. However, the NRC determined that they had not conducted full testing in accordance with the procedure, and only completed the instructions for returning the breaker to service.

## Source
- [Full enforcement letter (PDF)](https://www.nrc.gov/docs/ML1034/ML103410289.pdf)
- [NRC Reactor Licensees index](https://www.nrc.gov/reading-rm/doc-collections/enforcement/actions/reactors/)
---