← CPSC recalls

Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard

CPSC Recall1 injuries · 2012-02-15 · 12721

Hazards

On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.

Recall

Number
12721
Date
2012-02-15
Injuries reported
1

Products

Names
Fire Alarm Control Panel

Remedies

Options
New Instructions

Companies

Manufacturer(s)
Bosch Security Systems, Inc., of Fairport, N.Y.
Retailer(s)
Authorized distributors and installers nationwide from May 2009 through October 2011 for about $1,200.
Country of manufacture
China

Description

The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings.

Source

Authoritative
CPSC recall page
Machine
JSON-LD · Markdown