← CPSC recalls

SolarWorld Recalls Solar Systems with Copper Grounding Lugs Due to Electrocution, Electric Shock or Fire Hazard

CPSC Recall1 injuries · 2014-08-21 · 14260

Hazards

SolarWorld solar panels installed with bare-copper grounding lugs can corrode which could result in a faulty ground circuit, posing an electric shock, electrocution or fire hazard.

Recall

Number
14260
Date
2014-08-21
Injuries reported
1

Products

Names
SolarWorld Solar Systems

Remedies

Options
Repair

Companies

Retailer(s)
SolarWorld installers and distributors, or other distribution companies from June 2011 to June 2014 for about $1,000 to $10,000 depending on system size.
Distributor(s)
SolarWorld Americas, of Camarillo, California, a subsidiary of SolarWorld AG, of Bonn, Germany.
Country of manufacture
United States

Description

This recall includes SolarWorld solar systems installed with bare-copper grounding lugs installed after June 1, 2010. These solar systems use energy from the sun to generate electricity within a system circuit. The installation instructions for SolarWorld solar systems sold after June 1, 2010 called for the use of GBL-4DB lugs for grounding. SolarWorld has revised these installation instructions to explicitly call for tin-coated lugs, specifically Ilsco part number GBL-4DBT. "T" is for tin-coated and indicated by the silver color of the lug.

Source

Authoritative
CPSC recall page
Machine
JSON-LD · Markdown