CPSC, Liebert Corp. Announce Recall of Cooling System

CPSC Recall1 injuries · 2000-11-08 · 01503

Hazards

An electric heating element inside the system, that is used primarily in the dehumidification process, can short circuit and produce sparks, posing a smoke and fire risk.

Recall

Number
01503
Date
2000-11-08
Injuries reported
1

Products

Names
Mini-Mate2 Environmental Control Units

Companies

Manufacturer(s)
Liebert Corp., of Columbus, Ohio
Retailer(s)
Liebert Corp. sold these units nationwide, from January 1998 through August 2000, for between $3,000 and $8,000.

Description

The environmental control units are used as a cooling system in computer rooms. The recalled units are 277 volts and 1.5, 2 and 3 tons with electric reheat. The units are mounted in the ceiling and use ducts or special distribution grills to distribute the air.