← CPSC recalls

CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers

CPSC Recall1 injuries · 2002-10-02 · 03003

Hazards

A spring mechanism integrated with the damper is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Recall

Number
03003
Date
2002-10-02
Injuries reported
1

Products

Names
Siebe actuators

Companies

Distributor(s)
Invensys Building Systems, of Love Park, Ill.
Country of manufacture
United States

Description

These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947. See the associated recall alert for more details on the dampers and companies involved.

Source

Authoritative
CPSC recall page
Machine
JSON-LD · Markdown