# Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO
> **CPSC recall** · 2016-03-31 · 16134 · 1 injuries reported
## Recall
- **Number:** 16134
- **Date:** 2016-03-31
- **Injuries reported:** 1
## Products

Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)

## Hazards

When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.

## Remedies

Repair

## Retailer(s)

Authorized distributors from May 2015 through August 2015 for about $800.

## Country of manufacture

United States

## Description

This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

## Source
- [CPSC recall page](https://www.cpsc.gov/Recalls/2016/Gamewell-FCI-Recalls-Fire-Alarm-Panels)
---
*AI Analytics · CC0 1.0*