9/30/03 - COMPLAINT FILED, PROPOSING A PENALTY OF $71,740. COMPLAINT ALLEGES:
RESPONDENT FAILED TO ENSURE THAT ITS UST WAS STRUCTURALLY SOUND BEFORE INSTALLING A CATHODIC PROTECTION SYSTEM, IN VIOLATION OF RCRA 9006;
RESPONDENT FAILED TO HAVE ITS CATHODIC PROTECTION SYSTEM TESTED BY A QUALIFIED CATHODIC PROTECTION TESTER WITHIN 6 MONTHS OF INSTALLATION AND EVERY 3 YEARS THEREAFTER, IN VIOLATION OF RCRA 9003;
RESPONDENT FAILED TO INSPECT ITS IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM TO ENSURE PROPER OPERATION AT LEAST EVERY 60 DAYS, IN VIOLATION OF RCRA 9003;
RESPONDENT FAILED TO OPERATE ITS IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUOUSLY FOR CORROSION PROTECTION, IN VIOLATION OF RCRA 9003;
RESPONDENT FAILED TO MAINTAIN RECORDS OF OPERATION OF THE CATHODIC PROTECTION SYSTEM, IN VIOLATION OF RCRA 9003;
RESPONDENT FAILED TO PROVIDE ADEQUATE RELEASE DETECTION FOR ITS UST SYSTEM, IN VIOLATION OF RCRA 9003;
RESPONDENT FAILED TO MONITOR ITS USTs FOR RELEASES EVERY 30 DAYS, IN VIOLATION OF RCRA 9003;
RESPNDENT FAILED TO PROVIDE AN ADEQUATE AUTOMATIC LEAK DETECTION SYSTEM FOR ITS PRESSURIZED PIPING, IN VIOLATION OF RCRA 9003;
RESPONDENT FAILED TO MAINTAIN ANY RECORDS OF RELEASE DETECTION FOR ITS USTs AND ASSOCIATED PIPING, IN VIOLATION OF RCRA 9