← EPA enforcement cases

ERWIN PLANT, LLC

Administrative - Formal · FY2021 · — · Final Order With Penalty · 3602819443

Penalty
Cost recovery
Compliance action

Case

Case Number
04-2021-3200
Type
Administrative - Formal
Lead
EPA
Outcome
Final Order With Penalty
Multimedia
Self-disclosure
N

Defendants (1)

Summary

SEPTEMBER 7, 2021 - CONSENT AGREEMENT AND FINAL ORDER ISSUED: On November 21, 2019, an authorized agent of the EPA Region 4 conducted an inspection at the Facility pursuant to Section 15 of TSCA, 15 U.S.C. ? 2614, to determine the Facility's compliance with the PCB regulations. the EPA alleges that Respondent failed to: a. Conduct and/or document inspections checking for leaks at least once every 30 days for all PCB Transformers in storage. b. Have a proper storage area with an adequate roof, walls, and non-porous floor with curbing for all the PCB Transformers. c. Mark all the storage areas used to store PCB Transformers, except the area where the #29 transformer was being stored, with the appropriate PCB label. d. Mark all the PCB Transformers, with a date when they were removed from service for disposal. e. Dispose all the PCB Transformers, within 1-year from the date the PCB Transformers were determined to be PCB Waste. f. Notify the EPA of PCB Waste activities by filling out and submitting EPA Form 7710-53.