← CPSC recalls

Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO

CPSC Recall1 injuries · 2016-03-31 · 16134

Hazards

When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.

Recall

Number
16134
Date
2016-03-31
Injuries reported
1

Products

Names
Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)

Remedies

Options
Repair

Companies

Retailer(s)
Authorized distributors from May 2015 through August 2015 for about $800.
Distributor(s)
Gamewell-FCI of Northford, Conn.
Country of manufacture
United States

Description

This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

Source

Authoritative
CPSC recall page
Machine