← OSHA severe injury reports

Electrical burns, unspecified

1 hospitalization · 20181111296 · 11/2/2018 · Mesa Technical Associates, Inc

Severity

Hospitalized
1
Amputation
0
Loss of eye
0
Body part
Hand(s), unspecified
Nature of injury
Electrical burns, unspecified

Cause

Event
Direct exposure to electricity, greater than 220 volts
Source
Batteries other than automotive

Employer

Name
Mesa Technical Associates, Inc
Location
880 East 134th Street, BRONX, NEW YORK, 10454
NAICS
334515
Jurisdiction
1

Narrative

An employee was preparing to perform a load test on a battery system. He was receiving directions over the phone from the lead supervising technician. He and his co-worker were attempting to divide the 240-volt battery system into two 120-volt systems to perform the load test. His supervisor was directing them on where to divide the battery string. The system was then divided at cell 56 instead of cell 58. He was attempting to move the battery strap when the battery connector was placed on the terminal post, closing the 240-volt system. This created a short in the system, resulting in a DC arc flash that burned his left hand. Gloves were not worn at the time of the incident.

Source

Authoritative
OSHA Severe Injury Reports
Machine