← OSHA severe injury reports

Fractures and burns

1 hospitalization · 2024109962 · 10/26/2024 · Three Phase Line Construction Inc.

Severity

Hospitalized
1
Amputation
0
Loss of eye
0
Body part
Trunk and other upper extremities
Nature of injury
Fractures and burns

Cause

Event
Indirect exposure to electricity greater than 220 volts
Source
Power lines, transformers, convertors
Secondary source
Power lines, transformers, convertors

Employer

Name
Three Phase Line Construction Inc.
Location
Marcy Substation, MARCY, NEW YORK, 13403
NAICS
238210
Jurisdiction
1

Narrative

An employee was removing a jumper from the center phase of a de-energized transmission line. When the jumper was removed, the induction current on the line (induced by nearby energized transmission lines) entered the employee's left hand and exited through his left hip area. The employee was hospitalized with burn wounds to left hand and lower right abdomen, as well as a compression fracture to his T5, T6, and T7 vertebrae.